菲尼克斯防雷器FLT-CP-PLUS-3C-350
日期:2012-05-19 23:28 点击:460
价格:未填
供应:500
发货:3天内
Arrester rated voltage UC(L-PEN)| 350 V AC |
Nominal frequency fN| 50 Hz (60 Hz) |
Rated load current| 125 A (≤ 55°C) |
Nominal discharge surge current In (8/20) µs (L-PEN)| 25 kA |
| 75 kA (3L-PEN) |
Lightning test current (10/350) µs, charge| 37.5 As |
Lightning test current (10/350) µs, specific energy| 1.40 MJ/Ω |
Lightning test current (10/350) µs, peak value limp| 75 kA |
Lightning test current (10/350) µs, charge| 12.5 As |
Lightning test current (10/350) µs, specific energy| 160.00 kJ/Ω |
Lightning test current (10/350) µs, peak value limp| 25 kA (1L-PEN) |
Impulse operate voltage at 6 kV (1.2/50)µs (L-PEN)| ≤ 1.5 kV |
Protection level UP(L-PEN)| ≤ 1.5 kV |
Response time (L-N)| ≤ 100 ns |
Max. required backup fuse with branch wiring| 315 A (gL/gG) |
Max. required backup fuse with V-type through wiring| 125 A (gL/gG) |
Recommended backup fuse maximum| 160 A (gL/gG, 125 A with serial through wiring) |
Short circuit resistance ICCwith max. backup fuse (effective)| 50 kA |
Follow current quenching capacity If (L-PE)| 50 kA (264 V AC) |
| 25 kA (350 V AC) |
Connection, protective circuit
Type of connection| Screw terminal blocks |
Connection type IN| Biconnect screw terminal block |
Connection type OUT| Biconnect screw terminal block |
Connection method| Biconnect terminal block |
Screw thread| M5 |
Tightening torque, min| 4.5 Nm |
Stripping length| 18 mm |
Conductor cross section stranded min.| 2.5 mm² |
Conductor cross section stranded max.| 25 mm² |
Conductor cross section solid min.| 2.5 mm² |
Conductor cross section solid max.| 35 mm² |
Conductor cross section AWG/kcmil min.| 13 |
Conductor cross section AWG/kcmil max| 2 |